RT 682 Multivariable control: stirred tank

With RT 682 the complexities of a multivariable control system can be learned in a practical manner. The model for the controlled process is a typical application from process engineering: A chemical reaction taking place in a heated stirred tank. The reactants entering the stirred tank are pre-heated by the outflowing products in order to enhance energy efficiency.

Water is used as the product and reactant for RT 682. A pump transports the reactant out of a collecting tank via a heat exchanger into the stirred tank. The reactant is pre-heated by the heat exchanger. A heater in the double jacket permits control of the temperature in the stirred tank. Another pump transports the heated product out of the stirred tank via the heat exchanger back into the collecting tank. A bypass in the inlet routes the flow past the heat exchanger. A three-way motorised valve adjusts the ratio between the flow heated in the heat exchanger and the flow in the bypass. This is a further method of controlling the temperature in the stirred tank. A control valve changes the flow rate in the outlet and thus the level in the stirred tank. The temperature and level are mutually dependent variables. It is this dependence that makes this multivariable control system so complex.

Two industrial controllers are provided as temperature and level controllers. They can be configured and parameterised using a supplied software. The controllers have a Profibus DP interface. The interface permits monitoring of the trainer via an optionally available software RT 650.60. The RT 650.60 software also permits recording of the process variables and parameterisation of the controllers using the PC. It is also possible to interconnect multiple trainers from this series through the Profibus DP interface.

  • practical multivariable control of temperature and level in a stirred tank
  • typical application from process engineering with heat recovery
  • 2 configurable industrial controllers
  • optional process control software RT 650.60 available

Tanks

  • stirred tank: 15L
  • collecting tank: 70L

2 pumps

  • max. flow rate: approx. 60L/min
  • max. head: approx. 20m

Heat exchanger transfer surface: approx. 0,8m2
Heater power output: approx. 2kW
Temperature and level controller parameterisable as

  • P, PI or PID controller
  • switching controller

Measuring ranges

  • flow rate: 60…640L/h
  • temperature: 0…100°C
  • level: 0…1000mm
  • 3-way motorised valve opening: 0…100%

 

230V, 50Hz, 1 phase

  1. coupled level and temperature control in one stirred tank
  2. circuit with stirred tank, collecting tank and pump
  3. heat recovery with heat exchanger
  4. stirred tank with double jacket and heater; level display for tank and jacket
  5. temperature control with heater and 3-way motorised valve as actuators
  6. level control with pneumatic control valve as actuator
  7. temperature controller and level controller configurable and parameterisable with software
  8. 2-point controller for constant temperature in collecting tank via external cooling water
  9. optional process control software RT 650.60 via Profibus DP interface
  • coupled level and temperature control
  • level control with
    • PI controller
    • disturbance feedforward control
  • temperature control
    • with two-point controller
    • with three-point controller (split range)
    • with override control
    • via motorised valve with position feedback
  • plotting step responses